Rated Voltage 10kV & 35kV Insulated Aerial Cable
Uses:
The product is suitable to be used for power distribution and supply of electric transmission aerial line with power frequency rated voltage 10kV and 35kv. And the allowable long-term working temperature of cable conductor can be above:
High-density polyethylene insulated aerial cable: 75 0 C;
Cross-linked polyethylene insulated aerial cable: 90 0 C;
When short circuit occurs, (the longest sustained time not over 5 seconds) the highest temperature of cable conductor shouldn't be above:
High-density polyethylene insulated aerial cable: 150 0 C;
Cross-linked polyethylene insulated aerial cable: 250 0 C.
Model Number and Product Name:
Model Number |
Product Name |
JKYJ |
Copper-Core Cross-Linked Polyethylene Insulated Aerial Cable |
JKTRYJ |
Flexible Copper-Core Cross-Linked Polyethylene Insulated Aerial Cable |
JKLYJ |
Aluminum-Core Cross-Linked Polyethylene Insulated Aerial Cable |
JKLGYJ |
Steel-Core Aluminum-Stranded-Wire–Core & Cross-Linked Polyethylene Insulated Aerial Cable |
JKLHYJ |
Aluminum-Alloy-Core Cross-Linked Polyethylene Insulated Aerial Cable |
JKY |
Copper-Core Polyethylene Insulated Aerial Cable |
JKTRY |
Flexible Copper-Core Polyethylene Insulated Aerial Cable |
JKLY |
Aluminum-Core Polyethylene Insulated Aerial Cable |
JKLGY |
Steel-Core Aluminum-Stranded-Wire-Core Polyethylene Insulated Aerial Cable |
JKLHY |
Aluminum-Alloy-Core Polyethylene Insulated Aerial Cable |
JKLYJ/Q |
Aluminum-Core Light-Cross-Linked Polyethylene Thin-Insulated Aerial Cable |
JKLHYJ/Q |
Aluminum-Alloy-Core Light-Cross-Linked Polyethylene Thin-Insulated Aerial Cable |
JKLGY/Q |
Steel-Core Aluminum-Stranded-Wire-Core Light-Cross-Linked Polyethylene Thin-Insulated Aerial Cable |
JKLY/Q |
Aluminum-Core Light Polyethylene Thin-Insulated Aerial Cable |
JKLHY/Q |
Aluminum-Alloy-Core Light Polyethylene Thin Insulated Aerial Cable |
JKLGY/Q |
Steel-Core Aluminum-Stranded-Wire-Core Light Polyethylene Thin Insulated Aerial Cable |
Performance Characteristics:
DC resistance and insulation resistance of cable conductor is conformity to the following list:
Nominal Cross Section mm 2
|
200C DC Resistance Ω /km ≤ |
Insulation Resistance under Ambient Temperature
MΩ.km ≥ |
Breakage Pulling Force of Cable (Single-Core)
N |
Copper |
Aluminum |
Aluminum Alloy |
Aluminum Stranded Wire |
Hard |
Flexible |
10kV Light-Type |
10kV |
35kV |
Hard Copper |
Aluminum-Core |
Aluminum-Alloy-Core |
10 |
- |
1.83 |
3.08 |
- |
|
1000 |
1500 |
4100 |
- |
- |
- |
16 |
- |
1.15 |
1.91 |
- |
1.91 |
- |
- |
- |
25 |
0.749 |
0.727 |
1.20 |
1.303 |
1.20 |
8465 |
3762 |
6284 |
35 |
0.540 |
0.524 |
0.868 |
1.007 |
0.868 |
11731 |
5177 |
8800 |
50 |
0.399 |
0.387 |
0.641 |
0.744 |
0.641 |
16502 |
7011 |
12569 |
70 |
0.276 |
0.268 |
0.443 |
0.514 |
0.443 |
23461 |
10354 |
17596 |
95 |
0.199 |
0.193 |
0.320 |
0.371 |
0.320 |
31759 |
13727 |
23880 |
120 |
0.158 |
0.153 |
0.253 |
0.2964 |
0.253 |
39911 |
17339 |
30164 |
150 |
0.128 |
- |
0.206 |
0.239 |
0.206 |
49505 |
21033 |
37706 |
185 |
0.1021 |
- |
0.164 |
0.190 |
0.164 |
61846 |
26732 |
46503 |
240 |
0.0777 |
- |
0.125 |
0.145 |
0.125 |
79823 |
34679 |
60329 |
300 |
0.0619 |
- |
0.100 |
0.110 |
0.100 |
99788 |
43349 |
75411 |
Finished cable should stand the test of power frequency AC voltage:
Rated Voltage U |
10kV |
35kV |
Testing Voltage |
Ordinary Insulated Structural Cable
18kV/1min
Not Breakdown |
Light-Type Thin Insulated Structural Cable
12kV/1min
Not Breakdown |
63kV/1min