3.6/6kV~26/35kV Cross-Linked Polyethylene Insulated &

Flame Retarding Power Cable

 

Uses:
The product is suitable to be used for electrical distribution and supply of transmission line with power frequency rated voltage 3.6/6kV~26/35kV. And 900C is the allowable highest long-term operating temperature of cable conductor; the highest temperature of cable conductor can't be above 2500C when short circuit occurs.

Model Number and Product Name:


Type

Model Number

Product Name

 

Flame Retarding Power Cable

 

 

ZRA-YJV
ZRB-YJV
ZR(C )-YJV

Copper-Core Cross-Linked Polyethylene Insulated & PVC Sheathed Flame Retarding Power Cable

ZRA-YJLV
ZRB-YJLV
ZR(C )-YJLV

Aluminum-Core Cross-Linked Polyethylene Insulated & PVC Sheathed Flame Retarding Power Cable

 

ZRA-YJV22
ZRB-YJV22
ZR(C )-YJV22

Copper-Core Cross-Linked Polyethylene Insulated & Steel-Tape Armored & PVC Sheathed Flame Retarding Power Cable

ZRA-YJLV22
ZRB-YJLV22
ZR(C )-YJLV22

Aluminum-Core Cross-Linked Polyethylene Insulated & Steel-Tape Armored & PVC Sheathed Flame Retarding Power Cable

ZRA-YJV32
ZRB-YJV32
ZR(C )-YJV32

Copper-Core Cross-Linked Polyethylene Insulated & Thin Steel-Wire Armored & PVC Sheathed Flame Retarding Power Cable

ZRA-YJLV32
ZRB-YJLV32
ZR(C )-YJLV32

Aluminum-Core Cross-Linked Polyethylene Insulated & Thin Steel-Wire Armored & PVC Sheathed Flame Retarding Power Cable

Halogen-Free & Low-Fume Flame Retarding Power Cable

WDZA-YJY
WDZA-YJLY

Copper-Core (Aluminum-Core) Cross-Linked Polyethylene Insulated & Polyethylene Sheathed Halogen-Free & Low-Fume Flame Retarding Power Cable

WDZB-YJY23
WDZB-YJLY23

Copper-Core (Aluminum-Core) Cross-Linked Polyethylene Insulated & Steel-Tape Armored & Polyethylene Sheathed Halogen-Free & Low-Fume Flame Retarding Power Cable

WDZC-YJY33
WDZC-YJLY33

Copper-Core (Aluminum-Core) Cross-Linked Polyethylene Insulated & Thin Steel-Wire Armored & Polyethylene Sheathed Halogen-Free & Low-Fume Flame Retarding Power Cable

Selection of Rated Voltage of Cable:


If the rated voltage of cable is appropriate with the operation-state of cable-linking system, “U0/U (Um)” are indicated, all of them are effective values with application unit “kV”.
U0– rated power frequency voltage between ground cable conductor and metal screening material;
U- rated power frequency voltage between conductors of cable;
Um- the biggest value of the highest system-voltage of working cable.

Three-phase system-used rated voltage of cable as follows:

 

U

 

Um

U0

Category-I Cable

Category-II Cable

3

3.6

1.8

3.6

6

7.2

3.6

6

10

12

6

8.7

15

17.5

8.7

12

20

24

12

18

35

42

21

26

Note: Category-I------ used for single-phase ground connection, and the fault time of system is not over 1min each time and the longest one not over 8 hours, the total fault occurring hours of the system not over 125 hours every year.
Category-II------used for the system with longer time of ground connection fault and also adopted for the places required for relative high insulation performance of cable.


Performance Characteristics:
DC resistance and insulation resistance of cable conductor is in conformity to the following list:

Nominal Cross Section mm2

200C DC ResistanceΩ/km ≤

Copper

Aluminum

25

0.727

1.20

35

0.524

0.868

50

0.387

0.641

70

0.263

0.443

95

0.193

0.320

120

0.153

0.253

150

0.124

0.206

185

0.0991

0.164

240

0.0754

0.125

300

0.0601

0.100

400

0.0470

0.778

500

0.0366

0.0603

630

0.0283

0.0469

800

0.0221

0.0367

The self-discharge test with power frequency voltage of finished cable is in conformity to the following list:


No

Item for Test

Rated Voltage kV for Cable

3.6/6

6/6
6/10

8.7/10
8.7/15

12/20

18/20
18/30

21/35

26/35

1

AC Voltage of Power Frequency?? kV/5min

12.5

21

30.5

42

63

73.5
(53)*

91
(65)*

2

AC Voltage Test kV of Power Frequency for 4 Fours

14.4

24

35

48

72

84

104

3

Shock Voltage Test?? kV

60

75

95

125

170

200

250

4

Self-Discharge Test
Biggest Self-Discharge Quantity pC under 1.73 U0

5

5

5

5

5

5

5

*21/35kV and 26/35kV power frequency voltage test for cable can be made following the 2.5 U0 x 30min or 3.5 U0 x 15 min according to the requirements of users.

The flame retarding performance should be in conformity to the requirements of Category-A, B and C specified in the Standard of GB/T18380.3-2001 (same effect as IEC60331).
The halogen-free performance should be in conformity to the requirements specified in the Standard GB/T17650-1998 (same effect as IEC60754).
The low-fume performance should be in conformity to the requirements specified in the Standard of GB/T17651-1998 (same effect as IEC601034).