Cross-Linked Polyethylene Insulated
(Flame Retarding) Wire & Cable
Uses:
The product is suitable to be used for electrical apparatus, fixed wiring and flexible connecting electrical appliance with power frequency of rated voltage 450/750kV or less. Such flame retarding cable especially suits for the key places required high safety coefficient, such as nuclear power station, subway and high storied building etc.
Model Number and Product Name:
Model Number |
Product Name |
BYJ |
Copper-Core Cross-Linked Polyethylene Insulated Wire |
BLYJ |
Aluminum-Core Cross-Linked Polyethylene Insulated Wire |
BYJR |
Copper-Core Cross-Linked Polyethylene Insulated Flexible Cable |
BYJY |
Copper-Core Cross-Linked Polyethylene Insulated Polyolefine Sheathed Cable |
BLYJY |
Aluminum-Core Cross-Linked Polyethylene Insulated Polyolefine Sheathed Cable |
Performance Characteristics:
DC resistance of cable conductor and insulation resistance is in conformity to the following list:
Nominal Cross Section mm2 |
200C DC Resistance Ω/km ≤ |
Nominal Cross Section mm2 |
200C DC Resistance Ω/km ≤ |
Copper |
Aluminum |
Copper |
Aluminum |
0.08 |
247 |
- |
6 |
3.08 |
4.61 |
0.12 |
158 |
- |
10 |
1.83 |
3.08 |
0.2 |
92.3 |
- |
16 |
1.15 |
1.91 |
0.3 |
69.2 |
- |
25 |
0.727 |
1.20 |
0.4 |
48.2 |
- |
35 |
0.524 |
0.868 |
0.5 |
39.0 |
- |
50 |
0.387 |
0.641 |
0.75 |
26.0 |
- |
70 |
0.263 |
0.443 |
0.75 |
24.5 |
- |
95 |
0.193 |
0.320 |
1.0 |
19.5 |
- |
120 |
0.153 |
0.253 |
1.0 |
18.1 |
- |
150 |
0.124 |
0.206 |
1.5 |
13.3 |
- |
185 |
0.0991 |
0.164 |
1.5 |
12.1 |
- |
240 |
0.0754 |
0.125 |
2.5 |
7.98 |
- |
300 |
0.0601 |
0.100 |
2.5 |
7.41 |
12.1 |
400 |
0.0470 |
0.0778 |
4 |
4.61 |
7.41 |
|
|
|
Core intervals, gap between core and screening materials of finished cable should stand the test of power frequency DC voltage: 2500V x 5min.
Flame retarding cable can be manufactured following the Standard of GB/T18380.3-2001 (same effect with that of IEC60332) according to the requirements of users, and other specification can be designated with “”ZR-”. |